Celebrating 25 Years 1999-2024
Short Time Burning In-Line Deflagration Flame Arresters
CMC offers a range of KITO Armaturen GmbH inline short time burning bi directional deflagration flame arresters to prevent chain reactions in pipelines with potentially explosive gas-air mixtures.
H31N Bi-directional in Line deflagration flame arrester, short-time burning proof KITO® INE-I-…/…-1.2 KITO® INE-I-…/…-1.2-T (-TT)
- Bi-directional in-line deflagration flame arrester
- Short-time burning proof
- Designed for protection against deflagration of flammable liquids and gases
- Approved for explosion group IIA1 substances, MESG ≥ 1.14 mm
- Operational limits of 1.2 bar abs. pressure and 60 °C temperature
- Maximum ignition source distance limited to 50x inner pipe diameter
- Compatible with both horizontal and vertical pipe installations
- Optional temperature sensor for thermal load detection during operation
- Endurance against “stabilized burning” for up to 1.0 min max burn time
WANT MORE TECHNICAL DETAILS? DOWNLOAD OUR DATASHEET.
INTERESTED OR HAVE QUESTIONS? GET IN TOUCH WITH US NOW!
H32N Bi-directional in Line deflagration flame arrester, short-time burning proof KITO® INE-I-…/…-1.5 KITO® INE-I-…/…-1.5-T (-TT)
- Bi-directional in-line deflagration flame arrester
- Short-time burning proof
- Suitable for protection against deflagration of flammable liquids and gases
- Compatible with explosion group IIA1 substances, MESG ≥ 1.14 mm
- Operating parameters set to 1.5 bar abs. pressure and 60 °C temperature
- Ignition source distance restriction of 50x the inner pipe diameter
- Allows for installation in both horizontal and vertical orientations
- Optional temperature sensor for monitoring thermal load on element
- Designed to resist “stabilized burning” up to a 1.0 min maximum burn time
WANT MORE TECHNICAL DETAILS? DOWNLOAD OUR DATASHEET.
INTERESTED OR HAVE QUESTIONS? GET IN TOUCH WITH US NOW!
H33N Bi directional in line deflagration flame arrester, short-time burning proof KITO® EFA-Def0-I-…/…-1.2 KITO® EFA-Def0-I-…/…-1.2-T (-TT)
- Bi-directional in-line deflagration flame arrester
- Short-time burning proof
- Ensures protection of vessels and components against deflagration
- Approved for explosion group IIA1 substances, MESG ≥ 1.14 mm
- Operational limits at 1.2 bar abs. pressure and 60 °C
- Ignition source must not exceed 50x inner pipe diameter distance
- Compatible with both horizontal and vertical pipe installations
- Features optional one or two temperature sensors for short time burning protection, tBT = 1.0 min
- Placement of a single temperature sensor on the expected burning side
WANT MORE TECHNICAL DETAILS? DOWNLOAD OUR DATASHEET.
INTERESTED OR HAVE QUESTIONS? GET IN TOUCH WITH US NOW!
H 33.1 N Bi-directional In-line Deflagration Flame Arrester, Short-time Burning Proof KITO® CFA-Def0-I-…/…-1.2 KITO® CFA-Def0-I-…/…-1.2-T (-TT)
- Designed for bi-directional in-line deflagration flame arrester.
- Protects against deflagration of flammable liquids and gases.
- Approved for explosion group IIA1 substances with MESG ≥ 1.14 mm.
- Compatible with operating pressures up to 1.2 bar abs and temperatures up to 60 °C.
- Installation permissible in both horizontal and vertical pipes.
- Equipped with one or two temperature sensors for short-time burning protection (tBT = 1.0 min).
- Distance between ignition source and flame arrester must not exceed 50 times the inner pipe diameter.
- Holding design examination certificate to EN ISO 16852 and marked according to ATEX-Directive.
- Available with standard steel or stainless steel components, with customization options for materials and connections.
- Flow capacity data provided for air, with formulas for calculating flow for other gases.
WANT MORE TECHNICAL DETAILS? DOWNLOAD OUR DATASHEET.
INTERESTED OR HAVE QUESTIONS? GET IN TOUCH WITH US NOW!
H 33.3 N Bi-directional in-line deflagration flame arrester, short-time burning proof KITO® EFA-Def0-I-…/…-1.2-X16 KITO® EFA-Def0-I-…/…-1.2-X16-T (-TT)
- Application for protecting vessels/components against deflagration of flammable liquids and gases.
- Approved for substances of explosion group IIA1 with MESG ≥ 1.14 mm.
- Bi-directional operation in pipes with max operating pressure of 1.2 bar abs and temperature of 160°C.
- Installation permissible in both horizontal and vertical pipes.
- Can be equipped with one or two temperature sensors for short-time burning protection (tBT = 1.0 min).
- Operating distance from ignition source must not exceed 50 times the inner pipe diameter.
- Available with standard cast steel or stainless steel materials.
- Compatible with EN ISO 16852 and ATEX-Directive marked for safety compliance.
- Design allows for easy integration with existing pipe systems through flange connection.
- Uses PT 100 temperature sensor with a 3/8” connection in stainless steel.
WANT MORE TECHNICAL DETAILS? DOWNLOAD OUR DATASHEET.
INTERESTED OR HAVE QUESTIONS? GET IN TOUCH WITH US NOW!
H 34 N Bi-directional in-line deflagration flame arrester, short-time burning proof KITO® EFA-Def0-I-…/…-2.5 KITO® EFA-Def0-I-…/…-2.5-T (-TT)
- For protection against deflagration of flammable liquids and gases.
- Approved for explosion group IIA1 substances with MESG ≥ 1.14 mm.
- Bi-directional operation in pipes with a maximum of 2.5 bar abs pressure and 60 °C temperature.
- Installation allowed in both horizontal and vertical orientations.
- Equipped with temperature sensors for short-time burning protection, tBT = 1.0 min.
- Maximum distance from ignition source cannot exceed 50x inner pipe diameter.
- Constructed from materials such as standard and stainless steel, PTFE, and cast steel.
- Type examination certified according to EN ISO 16852 and ATEX Directive.
- Flow capacity calculations provided for air, with formulas for other gases.
WANT MORE TECHNICAL DETAILS? DOWNLOAD OUR DATASHEET.
INTERESTED OR HAVE QUESTIONS? GET IN TOUCH WITH US NOW!
H 34.2 N Bi-directional in-line deflagration flame arrester, short-time burning proof KITO® EFA-Def0-I-…/…-6.0 KITO® EFA-Def0-I-…/…-6.0-T (-TT)
- Designed for bi-directional deflagration protection in pipes.
- Suitable for flammable liquids and gases.
- Approved for explosion group IIA1 with MESG ≥ 1.14 mm.
- Operating limits: pressure 6.0 bar abs, temperature 60 °C.
- Installation allowed in horizontal and vertical pipes.
- Optional one or two temperature sensors for short-time burning protection (tBT = 1.0 min).
- Maximum distance from ignition source: 50 times the inner pipe diameter.
- Available in various sizes with dimensions specified for design configurations.
- Materials include standard and stainless steel options.
- Type examination certified to EN ISO 16852 and compliant with ATEX Directive.
WANT MORE TECHNICAL DETAILS? DOWNLOAD OUR DATASHEET.
INTERESTED OR HAVE QUESTIONS? GET IN TOUCH WITH US NOW!
H 35 N Bi-directional in-line deflagration flame arrester, short-time burning proof KITO® EFA-Def0-IIA-…/…-1.2 KITO® EFA-Def0-IIA-…/…-1.2-T (-TT)
- Designed for bi-directional deflagration protection in pipes.
- Suitable for flammable liquids and gases.
- Approved for explosion group IIA1 ot IIA with MESG ≥ 0.9 mm.
- Operating limits: pressure 1.2 bar abs, temperature 60 °C.
- Installation allowed in horizontal and vertical pipes.
- Optional one or two temperature sensors for short-time burning protection (tBT = 1.0 min).
- Maximum distance from ignition source: 50 times the inner pipe diameter.
- Available in various sizes with dimensions specified for design configurations.
- Materials include standard and stainless steel options.
- Type examination certified to EN ISO 16852 and compliant with ATEX Directive.
WANT MORE TECHNICAL DETAILS? DOWNLOAD OUR DATASHEET.
INTERESTED OR HAVE QUESTIONS? GET IN TOUCH WITH US NOW!
H 35.1 NBi-directional in-line deflagration flame arrester, short-time burning proof KITO® CFA-Def0-IIA-…/…-1.2 KITO® CFA-Def0-IIA-…/…-1.2-T (-TT)
- Designed for bi-directional deflagration protection in pipes.
- Suitable for flammable liquids and gases.
- Approved for explosion group IIA1 to IIA with MESG ≥ 0.9 mm.
- Operating limits: pressure 1.2 bar abs, temperature 60 °C.
- Installation allowed in horizontal and vertical pipes.
- Optional one or two temperature sensors for short-time burning protection (tBT = 1.0 min).
- Maximum distance from ignition source: 50 times the inner pipe diameter.
- Available in various sizes with dimensions specified for design configurations.
- Materials include standard and stainless steel options.
- Type examination certified to EN ISO 16852 and compliant with ATEX Directive.
WANT MORE TECHNICAL DETAILS? DOWNLOAD OUR DATASHEET.
INTERESTED OR HAVE QUESTIONS? GET IN TOUCH WITH US NOW!